3M 2131-217G Scotchcast Flame Retardant Compound 2131B, 213 g (7.5 oz), 10/Case 7000006239
3M 2131-217G Scotchcast Flame Retardant Compound 2131B, 213 g (7.5 oz), 10/Case 7000006239
3M 2131-217G Scotchcast Flame Retardant Compound 2131B, 213 g (7.5 oz), 10/Case 7000006239

3M 2131-217G Scotchcast Flame Retardant Compound 2131B, 213 g (7.5 oz), 10/Case 7000006239

3M SKU: AC ECO 2131-217G
Regular price $94.12
/

Sold in multiples of 10 Each(s)

Shipping calculated at checkout.

Standard
Usually ships in 6 days

  • Secure payments

Flame-retardant electrical insulating resin

Tough, flexible protection for demanding cable repairs

3M™ Scotchcast™ Flame Retardant Compound 2131B is a two-part polyurethane resin designed to replace or repair cable jackets and protect electrical connections in rugged operating environments. Once cured, the black compound provides a semi-flexible, flame-retardant barrier with strong electrical insulation, moisture sealing, and mechanical protection.

  • Two-part polyurethane resin
  • 213 g closed mixing pouch
  • Rated up to 1 kV
  • 10 pouches per case

Built for electrical protection in rugged conditions

Scotchcast™ 2131B combines electrical insulating performance with the flexibility and toughness required for mine, portable, single-core, and multi-core power cables. The closed pouch keeps both components separated until use and supports mixing and pouring without open-container measuring.

Flame-retardant protection

The cured resin forms a flame-retardant layer suited to cable jacket replacement, splice insulation, and electrical potting applications.

Tough and semi-flexible

Typical 82 Shore A hardness and 339% elongation help the cured material withstand movement, thermal shock, and mechanical shock.

Electrical insulation

High dielectric strength supports insulation in low-voltage cable splices operating at up to 1 kV.

Moisture sealing

The permanent polyurethane resin provides multipurpose sealing and bonds to itself and many modern cable-jacket materials.

Recommended applications

  • Replacing or repairing single-core and multi-core cable jackets
  • Mine and portable cable splice protection
  • Insulating conductors in splices operating up to 1 kV
  • Sealing cable crotches and sheaths at terminations
  • Potting cable fittings, wire encasements, and junction boxes
  • Potting printed circuit boards, back-shell connectors, and motor repairs

Key performance features

The resin is designed for electrical sealing, insulation, and mechanical protection. Always evaluate compatibility and follow the applicable 3M kit or installation instructions for the cable construction and voltage class.

Flame-retardant Semi-flexible Room-temperature cure Moisture sealing High dielectric strength Thermal-shock resistant Mechanical-shock resistant RoHS compliant

Technical specifications

Product type Two-part flame-retardant electrical insulating resin
Resin chemistry Polyurethane
Cured colour Black
Cured flexibility Semi-flexible
Package size 213 g (7.5 oz) closed mixing pouch
Case quantity 10 pouches
Voltage class Low voltage, up to 1 kV
Typical gel time 17 minutes at 23°C (73°F)
Typical hardness 82 Shore A, ASTM D2240
Typical tensile strength 1,038 psi, ASTM D412
Typical elongation 339%, ASTM D412
Typical dielectric strength 343 V/mil (13.5 kV/mm), ASTM D149
Temperature rating 90°C (194°F) continuous; 130°C (266°F) overload
3M catalogue number 2131-217G
3M stock number 7000006239
UPC 00051128591666
Country of origin United States

Technical values are typical only and are not intended as minimum, maximum, or specification values. Performance and cure behaviour depend on temperature, mixing quality, installation method, cable construction, and application conditions.

Typical de-mould and cure times

Temperature Typical de-mould time Approximate cure time
21°C (70°F) 1.5 to 2 hours 16 to 24 hours
10°C (50°F) 3.5 to 4 hours 24 to 30 hours
0°C (32°F) 6 to 8 hours 36 hours or longer

Times are typical. Confirm that the compound is no longer tacky and has developed suitable hardness before de-moulding or returning the repair to service.

Storage and handling

  • Keep the pouch sealed in its protective envelope until immediately before use.
  • In cold conditions, warm the closed pouch to at least 16°C (60°F) before mixing.
  • Mix until the resin reaches a completely uniform colour and consistency, following the applicable 3M instructions.
  • Store factory-sealed packages at 10°C to 27°C (50°F to 80°F) and below 75% relative humidity.
  • Typical shelf life is three years from the manufacturing date when stored as directed.

Important electrical and chemical safety information

De-energize, lock out, and ground all electrical systems before installation. Work should be performed by personnel trained in safe electrical practices and familiar with the applicable splice, repair, or potting procedure.

This two-part chemical system can cause serious health effects. Avoid breathing vapours, use adequate ventilation, and wear the eye, face, skin, and respiratory protection required by the current Safety Data Sheets and workplace exposure assessment. Review the product label, both component Safety Data Sheets, and the applicable 3M installation instructions before handling or use.

Frequently asked questions

What is 3M™ Scotchcast™ 2131B used for?

It is used to replace or repair cable jackets, insulate conductors in low-voltage cable splices, seal cable crotches and sheaths, and pot electrical components such as cable fittings, junction boxes, printed circuit boards, connectors, and motor repairs.

Does the pouch contain both resin components?

Yes. The product is a two-part polyurethane resin supplied in a closed mixing pouch. The components remain separated until the internal barrier is broken and the pouch is mixed according to 3M instructions.

How long does Scotchcast™ 2131B take to cure?

At 21°C (70°F), typical de-mould time is 1.5 to 2 hours and approximate cure time is 16 to 24 hours. Lower temperatures extend both times. Confirm cure by tack and hardness rather than time alone.

What voltage and temperature ranges does it support?

3M identifies the resin for cable-splice insulation operating at up to 1 kV, with a continuous temperature rating of 90°C (194°F) and an overload rating of 130°C (266°F). The complete installation must follow the applicable cable and splice-system requirements.